Electric Power

  • Specs Summary
  • Minimum Rating
    2750 kVA
  • Maximum Rating
    3000 kVA (3100 kVA without fan)
  • Prime
  • Standby

3516E Low Voltage Generator Set

Producing reliable power from 2750 kVA to 3000 kVA (3100 kVA without fan) at 50 Hz, our 3516E diesel generator sets are made to match your mission critical, standby and prime applications, and meet our quality standards. We’ve engineered each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Seismic certification is also available for select models, maintaining power after unexpected disturbances. The integrated control system, including ATS and switchgear, ensures a consistent power supply and connection to your fleet through on-site and remote monitoring options. Our EMCP 4 control panel provides flexible options, with a user-friendly interface, putting your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to provide expanded capacity and generator set redundancy to match your requirements. No two power needs are the same, which is why we offer a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging options to work with your spatial requirements and environmental conditions. Our 3516E generator sets are built to take on power challenges — customize them to take on yours.

Generator Set Specifications

  • Minimum Rating 2750 kVA
  • Maximum Rating 3000 kVA (3100 kVA without fan)
  • Voltage 380 to 415 volts
  • Frequency 50 Hz
  • Speed 1500 RPM

Generator Set Configurations

  • Emissions/Fuel Strategy Low Fuel Consumption

Engine Specifications

  • Engine Model 3516E, SCAC, V-16, 4-Stroke, Water-Cooled Diesel
  • Bore 6.69 (170 )
  • Stroke (HD) 8.46 (215 )
  • Compression Ratio 14:1
  • Aspiration TA
  • Governor Type Adem™5
  • Fuel System Electronic unit injection

Generator Set Dimensions

Standard Equipment

Air Inlet

  • Air Cleaner

Cooling

  • Package mounted radiator

Exhaust

  • Exhaust flange outlet

Fuel

  • Primary fuel filter with integral water separator
  • Secondary fuel filter
  • Fuel priming pump

Generator

  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection

Power Termination

  • Bus Bar

Control Panel

  • EMCP 4 Genset Controller

General

  • Paint - Caterpillar Yellow except rails and radiators gloss black

Starting/Charging

  • Heavy-duty starting system
  • Charging alternator

Optional Equipment

Exhaust

  • Exhaust mufflers
  • Exhaust expanders
  • Flexible fittings

Generator

  • Anti-condensation heater
  • Excitation: [ ] Permanent Magnet Excited (PM)

Power Termination

  • Circuit breakers, IEC compliant

Control Panels

  • EMCP (4.2) (4.3) (4.4)
  • Generator temperature monitoring & protection
  • Load share module
  • Digital I/O module
  • Remote monitoring software

Mounting

  • Rubber anti-vibration mounts
  • Spring-type vibration isolator
  • IBC isolators

Starting/Charging

  • Battery chargers
  • Oversize batteries
  • Jacket water heater

General

  • The following options are based on regional and product configuration:
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • EU Certificate of Conformance (CE)
  • EEC Declaration of Conformity
  • Enclosures: sound attenuated, weather protective
  • Automatic transfer switches (ATS)
  • Integral & sub-base fuel tanks