Electric Power

  • Specs Summary
  • Minimum Rating
    27.0 ekW (33.8 kVA)
  • Maximum Rating
    60.0 ekW (75 kVA)
  • Prime
  • Standby

C3.3 Generator Set

Providing reliable energy solutions, our C3.3 diesel generator sets are made to meet your standby and prime applications. Dedicated single phase and three phase models are available. All standby C3.3 generator sets are supplied with 4 years extended service coverage as standard. We’ve designed each to ISO 8528-5 transient response requirements. C3.3 generator sets are available with a choice of emissions levels from non regulated up to EU Stage IIIA emissions compliant. We offer easy-to-use Cat control panels, EMCP 4.1 or EMCP 4.2 options. Browse a broad range of accessories including galvanised sound attenuated enclosures and integral fuel tanks. Our C3.3 generator sets are made for demands, so you can make yours.

Generator Set Specifications

  • Minimum Rating 27.0 ekW (33.8 kVA)
  • Maximum Rating 60.0 ekW (75 kVA)
  • Voltage 110 to 480 Volts
  • Frequency 60 Hz
  • Speed 1800 RPM

Generator Set Configurations

  • Emissions/Fuel Strategy Non Regulated, EU Stage II and EU Stage IIIA

Engine Specifications

  • Engine Model Cat® C3.3
  • Bore 4.1 (105 )
  • Displacement 201.4 (3.3 )
  • Stroke 5 (127 )
  • Compression Ratio 17.25:1, 19.25:1
  • Governor Type Mechanical
  • Fuel System Direct Injection

Generator Set Dimensions

Standard Equipment

Air Inlet System

  • Air cleaner; light duty with disposable element

Control Panel

  • EMCP4.1 control panel

Cooling System

  • Radiator and cooling fan with guards
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant

Exhaust System

  • Stub pipe, gaskets, raincap & SAE exhaust flange for customer use; shipped loose

Fuel System

  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank

Generators and Generator Attachments

  • 12 leads
  • IP23 Protection
  • Voltage regulator (single phase sensing)
  • Tower panel, IP22, bottom cable entry
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • Segregated low voltage (AC/DC) wiring panel

Governing System

  • Mechancial governing system - model dependant

Lube System

  • Lubricating oil
  • Oil drain line with valve

Mounting System

  • includes lifting provisions and termination points for coolant
  • Captive linear vibration isolators between base and engine-generator
  • Termination points for coolant and lube oil drain lines

Starting / Charging System

  • 12V battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar Yellow

Optional Equipment

Alternator

  • Alternator removal options
  • R frame auxilliary winding - SE AUx Alt 01, 02 and 03
  • LC frame alternator
  • LC frame alternator with coastal protection
  • Permanent magnet
  • Anti-condensation heater

Circuit Breakers

  • 4 Pole circuit breaker

Control Panel Options

  • Volt free contacts for common alarm
  • Volt free contacts for genset running
  • Speed adjust potentiometer - requires electronic govenor
  • Voltage adjust potentiometer
  • Panel mounted audible alarm
  • Earth fault (2 wire only)
  • Earth leakage (2 wire only)
  • Overload shutdown via breaker
  • Battery charger
  • Emergency stop with key
  • Control panel heater

Cooling System

  • Coolant heater
  • Low coolant temperature alarm
  • low coolant level shutdown

Global Certifications

  • Certification for CIS

Enclosures

  • Sound attenuated level 2 enclosure CE
  • Sound attenuated level 1 enclosure (GALV)

European Certifications

  • Upgrade to STD set for "CE"

Fuel System

  • Open set narrow tankbase
  • Compact skidbase for open sets
  • Skidbase for CALG enclosure sets
  • DEFRA bunded fuel tank
  • Low fuel level shutdown
  • Low fuel level alarm
  • High fuel level alarm

Mounting Options

  • Electronic governor
  • Battery removal
  • Industrial silencer removal
  • Residential Silencer
  • Silencer installation kit

Rental Options

  • External single point lift - enclosure
  • Rental pack (CAE only)
  • CEE form sockets for enclosure
  • Socket blanking plate

General

  • Stone guards / rad trans flange
  • Packing case, compact set
  • Packing case compact set, canopied